Voltage Drop Scenario #2 For a load, the conductors consist of two 12 AWG THHN/THWN solid coated copper conductors connected to a 2-pole breaker in a 120/208-volt, 3Ø, 4-wire panelboard. The circuit serves a load that draws 9.8 amps. The distance between the panel and the load is 150 feet. Refer to Voltage Drop Scenario #2. Use NEC® Table 8 resistance to find the voltage dropped in the conductors and then determine the voltage applied to the load. The voltage applied to the load is ___ volts.